Power conditioning
Power-Sure 800
Power conditioner,
250–25,000 VA
Applications
• Datacenters
• Medicalapplications
• Sensitiveelectronicequipment
• Industrialfacilities
Characteristics
Technology Ferroresonant
Rating(VA) 250–25,000
Lineregulation ±2%V-outfor+10%to-20%V-inat100%load
Loadregulation ±3%for0%to100%load
Immunitytodistortion @40%THDV-in,5%maxTHDV-out
Ride-throughcapability 1cycle
Voltagerecovery 2cyclesto95%,3cyclesto100%
K-factor K-30rated
Powerfactor Inputof0.95typical
correction
Harmonicattenuation -23dBforloadreflectedharmonics
Galvanicisolation NEC250-5d,0.001PF
Surgeprotection UL1449rating,330V;ANSI/IEEE62.41-CatB3
Commonmode 140dB
noiseattenuation
Transversemode 120dB
noiseattenuation
Reliability 200,000hours(MTBF)
Audiblenoise 52–56dBmeasuredat1m,Ascale
Efficienty Approximately92%atfullload
Warranty Twoyears,10-yearcoreandcoilwarranty
Features
• Provenreliability
• Superiorisolation
• Tightvoltageregulation
• Highimmunitytodistortion
• Lightningandsurgeprotection
• Protectsagainstpowerinterruptions
• Powerfactorcorrection
• Bi-directionalharmonicfiltering
• Ride-throughcapability
Options
• Customoutputreceptacles(5–15kVAofficemodelsonly)
Model chart
Dimensions
Model types Voltage (VA) (H x W x D, in)
Officemodels 250,500,700,850 8.5x12.8x9.5
plug-and-play 1,000,1,600,2,100,2,500,3,500 8.5x12.8x17.5
5,000,7,500,10,000,15,000 15.0x23.8x22.5
Industrialmodels 250 8.5x10.5x8.0
Hardwired wall-/ 500,750,1,000 9.0x14.0x10.0
panel-mount 1,500,2,000,3,000 13.0x16.5x14.8
5,000,8,000,10,000 27.0x22.5x28.5
Industrialmodels 5,000,8,000,10,000 23.0x20.0x28.5
Hardwired 15,000,20,000,25,000 35.0x25.0x39.5
floor-mount
• Processcontrol
• Instrumentation
• Roboticcontrol
• MeetsANSIstandardsfor
computers—inputsaslowas
50%ofnominal
• UL1012,UL544andcULlisted
• Low-costinstallation
• Quietoperation
• Isolationandregulation
• Shortcircuit-proof
• Removalofharmonics