MGE UPS SYSTEMS - Galaxy 3000 Specification 11 Effective: September, 2006
§ load powered by UPS
6. MultiSlot Communications Card Expander (66071): The MultiSlot shall provide three additional
communication slots. The U-Talk Acquisition Card (66063) is included.
E. Network Based Power Management Software:
1. Solution-Pac 2 software shall facilitate the management of the UPS over any point in a wide area
network (WAN) or local area network (LAN). The software shall use a distributed, TCP/IP based
architecture and must be SNMP manageable. To reduce the volume of network traffic, the
software will employ trap reception acknowledgement. The software must be capable of graceful
server shutdown of individual or multiple servers from any point on the network for up to 50 servers
per card.
2. Enterprise Power Manager software shall facilitate the management of the UPS and servers over
any point in a wide area network (WAN) or local area network (LAN). The software shall provide
an overall, consolidated view of the main operating parameters of all power devices on the
network. The information shall be accessible from any workstation using a standard web browser.
The software shall use Secure Sockets Layer (SSL) and several levels of password protection for
complete security. MGE network device required.
F. Input Isolation Transformer: A delta zigzag input isolation transformer can be provided inside the
standard UPS cabinet to isolate the rectifier input and DC bus for ungrounded DC systems. Input
isolation transformers shall be standard on UPSs with input voltages other than 208 V.
G. Distribution Panelboards: Optional 24 or 42 pole front facing distribution panelboards will be
provided with the UPS in a matching adjacent cabinet. The panelboard will be a Square D, NQO panel
accommodating 10-100 amp breakers. Panelboards will accommodate any combination of one, two or
three pole breakers. The 24 pole panelboard system shall be provided in conjunction with the
maintenance bypass offering and shall be housed in the same cabinet. The 42 pole distribution shall be
housed in an independent cabinet.
H. Two or Three Circuit Breaker External Maintenance Bypass in Matching Cabinet: The maintenance
bypass option provides for two (2) or three (3) circuit breakers mounted in a matching, adjacent cabinet to
provide a wrap around bypass configuration for total UPS isolation during maintenance. Maintenance
bypass transfers shall be without interruption and shall have mechanical keyed interlocks to protect the
UPS from damage in the event of out of sequence transfers. An optional electrically based solenoid
activated key release shall be available to control the removal of the keys from the key interlocks.
I. Two or Three Circuit Breaker External Maintenance Bypass Wall Mount: The maintenance bypass
option provides for two (2) or three (3) circuit breakers mounted inside a wall mounted enclosure to
provide a wrap around bypass configuration for total UPS isolation during maintenance. Maintenance
bypass transfers shall be without interruption and shall have mechanical keyed interlocks to protect the
UPS from damage in the event of out of sequence transfers. An optional electrically based solenoid
activated key release shall be available to control the removal of the keys from the key interlocks.
J. Remote Alarm Status Panel: A wall mounted panel, 17.5”Hx12”Wx4”D, with eight (8) indicating
LED's shall display UPS status and any active alarms. The alarms shall be a latching type, such that if
an alarm is triggered, the LED will stay ON (latch) even if the alarm is corrected. This feature will
provide the operator the chance to verify the occurrence of the alarm. The parameters monitored and
controls provided on the RASP panel include:
1. UPS on line (Green LED)
2. UPS on battery (Yellow LED)
3. Load on bypass (Yellow LED)
4. UPS Summary alarm (Red LED)
5. Low Battery shutdown
The Remote Alarm Status Panel shall also be equipped with: