MGE UPS SYSTEMS - Galaxy 3000 Specification 12 Effective: September, 2006
» Alarm Test/Reset push-button: (white LED) to reset the latching alarm
» Audible Alarm: for alarm annunciation
» Audible Alarm reset push-button: (white LED) to silence the audible alarm
The RASP door shall be equipped with a key lock. The recommended maximum distance from the
UPS module shall be 500 feet.
K. Remote Summary Alarm Panel: A wall mounted panel with five (5) indicating LED's shall display UPS
status and any active alarms. The alarms shall be a latching type, such that if an alarm is triggered, the
LED will stay ON (latch) even if the alarm is corrected. This feature will provide the operator the
chance to verify the occurrence of the alarm. The parameters monitored and controls provided on the
RSAP panel include:
1. UPS summary alarm (Red LED)
2. UPS on battery (Yellow LED)
The Remote Summary Alarm Panel shall also be equipped with:
» Alarm Test/Reset push-button: (white LED) to reset the latching alarm
» Audible Alarm: for alarm annunciation
» Audible Alarm reset push-button: (white LED) to silence the audible alarm
The RSAP door shall be equipped with a key lock. The recommended maximum distance from the
UPS module shall be 500 feet.
L. Seismic Anchors: Seismic Zone 4 anchors shall be available for all system cabinets.
M. Dual Input: A second input terminal block shall be provided to accommodate a separate input source.
5.0 FIELD QUALITY CONTROL & SERVICE ORGANIZATION
5.1 FIELD SERVICE ENGINEER QUALIFICATIONS
The manufacturer must employ a 7 X 24 nationwide (international where applicable) field service organization
with rapid access to all regions of the nation. The responding service professionals must be factory-trained
engineers with an accredited and proven competence to service three phase UPS.
5.2 SPARE PARTS
Field Engineers must have immediate access to recommended spare parts with additional parts storage
located in regional depots. Additional spare parts shall be accessible on a 7 x 24 basis from the national
depot and must be expedited on a next available flight basis or via direct courier (whichever mode is
quickest).
5.3 MAINTENANCE TRAINING
The manufacturer shall make available to the customer various levels of training ranging from basic UPS
operation to UPS maintenance.
5.4 MAINTENANCE & SERVICE CONTRACTS
The manufacturer shall offer additional preventative maintenance and service contracts covering both the
UPS and the battery bank. Accredited professional service engineers employed exclusively in the field of
critical power systems service shall perform all maintenance and service. The manufacturer shall also offer
extended warranty contracts.