MGE UPS Systems 11+ User Manual

Browse online or download User Manual for Uninterruptible power supplies (UPSs) MGE UPS Systems 11+. MGE UPS Systems 11+ User manual

  • Download
  • Add to my manuals
  • Print

Summary of Contents

Page 1 - EX RT 5/7/11 Systems

www.eaton.comEX RT 5/7/11 SystemsInstallation and User Manual

Page 2

86-86000-00 B02 - Page 8IMPORTANT SAFETY INSTRUCTIONSSAVE THESE INSTRUCTIONS. This manual contains important instructions that should be followed duri

Page 3

86-86000-00 B02 - Page 9CAUTION: Safety of personsThe system has its own power source (the battery). Consequently, the power outlets may be energized

Page 4 - 86-86000-00 B02 - Page 2

86-86000-00 B02 - Page 10CAUTION: Record All Serial Numbers!RECORD ALL SERIAL NUMBERS FOR EX RT 5/7/11 AND ACCESSORIES. THESE SERIAL NUMBERS WILL BE R

Page 5 - Contents

86-86000-00 B02 - Page 11Symbol UsageThis manual uses the following icon symbols with text to convey important information and tips.WARNINGIndicates i

Page 6 - 5. Appendices

86-86000-00 B02 - Page 12(This page left blank intentionally)

Page 7 - 86-86000-00 B02 - Page 5

86-86000-00 B02 - Page 131. IntroductionThank you for selecting an EATON product to protect your electrical equipment.The product you selected is a pa

Page 8 - 86-86000-00 B02 - Page 6

86-86000-00 B02 - Page 141. IntroductionTable 1-2: Optional Accessories (See Section 1.5 for description)Part NumberDescription86001 Rail Kit for Powe

Page 9 - 86-86000-00 B02 - Page 7

86-86000-00 B02 - Page 151. Introduction1.1 System Electrical Characteristics Table 1-3: UPS Characteristics System Ratings.UPS CharacteristicsMAIN

Page 10 - IMPORTANT SAFETY INSTRUCTIONS

86-86000-00 B02 - Page 161. IntroductionTable 1-5: Battery Module Ratings.Part Number 86207 86209Battery Type 12 VDC/7 Ah 12 VDC/9 AhBattery Output Vo

Page 11 - CAUTION: Safety of persons

86-86000-00 B02 - Page 171. Introduction1.2.2 Rack ConfigurationFigure 1-2: Rack Configuration with Power Module, Battery Module, and optional Trans

Page 13 - Symbol Usage

86-86000-00 B02 - Page 181. Introduction1.3 Rear Panel Components1.3.1 Power Module EX RT 5/7/11Figure 1-3: Rear panel of the Power Module.1.3.2 B

Page 14 - 86-86000-00 B02 - Page 12

86-86000-00 B02 - Page 191. Introduction1.3.3 EX RT Transformer Module Figure 1-5: Rear Panel of the optional Transformer Module (PN 86211/86311)Mai

Page 15 - 1. Introduction

86-86000-00 B02 - Page 201. Introduction1.5 Optional AccessoriesOptional Accessories describes the options available for upgrades and enhancement of

Page 16

86-86000-00 B02 - Page 211. Introduction1.5.3 Multiple Battery Module Back-up Time at Full LoadStandard EX RT 5/7/11 systems (one Power Module and on

Page 17

86-86000-00 B02 - Page 221. Introduction1.5.5 Battery Integration Kit with Casters(Part number 86005) Battery Integration Kit is a cart, designed to

Page 18

86-86000-00 B02 - Page 231. Introduction1.5.7 Transformer Module - For use with EX RT 5/7/11 Power ModuleThis module provides isolated 120/208/240 VA

Page 19

86-86000-00 B02 - Page 241. Introduction1.5.8 CLA Charger ModuleExtended back-up time (up to 8 hours at full load) requires a high power battery cabi

Page 20

86-86000-00 B02 - Page 252. Setup and Installation2.0 ScopeSetup and Installation guides the user through tools and equipment required for connecting

Page 21

86-86000-00 B02 - Page 262. Setup and Installation2.2 Contents of Standard EX RT 5/7/11 Systems Contents of EX RT 5/7/11 Power Module (PN 86215 / 862

Page 22

86-86000-00 B02 - Page 272. Setup and InstallationContents of EX RT EXB 5/7/11 Battery Module: (PN 86207 /86209)29 Stabilizer Bracket and hardware.38

Page 23 - 86-86000-00 B02 - Page 21

EX RT 5/7/11 SystemsInstallation and User ManualRevision HistoryEX RT 5/7/11 Systems Installation and User Manual, 86-86000-00Revision: A01 ECN#: 0

Page 24

86-86000-00 B02 - Page 282. Setup and Installation2.3 Installation in Tower ConfigurationFollow the numerical sequence to assemble tower stands and t

Page 25 - Quick Start

86-86000-00 B02 - Page 292. Setup and Installation2.4 Installation in Rack Mounting Configuration2.4.1 Adjustment of Front Panel Logo and Control Pa

Page 26 - CLA Rail Kit

86-86000-00 B02 - Page 302. Setup and Installation2.4.2 Prepare Battery Module for Rack Mounting IMPORTANTThis step requires two people.The Battery M

Page 27 - 2. Setup and Installation

86-86000-00 B02 - Page 312. Setup and Installation2.4.3 Power, Battery, Transformer, and CLA Charger Module Rack MountingThe following steps apply to

Page 28 - (see 1.5.1)

86-86000-00 B02 - Page 322. Setup and InstallationNOTEThis step is unique to the Power Module. It involves the installation of the I/O Box Bracket S

Page 29

86-86000-00 B02 - Page 332. Setup and Installation2.5 Communication PortsEX RT 5/7/11 Power Module provides 3 communication method’s that can be used

Page 30 - 86-86000-00 B02 - Page 28

86-86000-00 B02 - Page 342. Setup and Installation2.5.2 Connecting the Dry (Relay) Contact Communication Port 2 The system status is indicated by the

Page 31 - (rack orientation)

86-86000-00 B02 - Page 352. Setup and InstallationA wide range of optional cards will allow your UPS to talk to nearly all equipment management system

Page 32

86-86000-00 B02 - Page 362. Setup and Installation2.6 Remote Emergency Power Off (REPO) Communication Port 3 The end user is responsible for the inst

Page 33

86-86000-00 B02 - Page 372. Setup and Installation2.7 System ConnectionsWARNINGThis type of connections must be carried out by qualified electrical p

Page 34 - Install input/output cables

86-86000-00 B02 - Page 2(This page left blank intentionally)

Page 35

86-86000-00 B02 - Page 382. Setup and InstallationProceed as follows:1. For normal AC input, make connections to L1, L2, and terminals only. No conn

Page 36

86-86000-00 B02 - Page 392. Setup and Installation2.7.2 Connecting EX RT Transformer Module Part number 86211/86311This module is to provide isolated

Page 37

86-86000-00 B02 - Page 402. Setup and Installation2.7.3 Connections with Separate Normal and Bypass AC Sources (2 Mains)CAUTIONThis connection requir

Page 38 - 86-86000-00 B02 - Page 36

86-86000-00 B02 - Page 412. Setup and Installation2.7.4 System Connections as Frequency Converter (without Bypass AC source)Figure 2-15: Accessing T

Page 39 - - Max. 6AWG (EX RT 5/7)

86-86000-00 B02 - Page 422. Setup and Installation2.8 Connection of Battery Module EXB1. Check that the battery circuit breaker (5) 14 is OFF (“0”)

Page 40

86-86000-00 B02 - Page 432. Setup and Installation2.9 Connection of Optional CLA Module1. Connect the battery power cable 40 and battery detection c

Page 41

86-86000-00 B02 - Page 44(This page left blank intentionally)

Page 42

86-86000-00 B02 - Page 453. Operation3.0 ScopeOperation describes EX RT 5/7/11 systems characteristics of indicators and controls, modes and specific

Page 43

86-86000-00 B02 - Page 463. Operation3.2 UPS PersonalizationWARNINGBefore changing items from Tables, 3-1, 3-2, 3-3, and 3-4, the UPS system mus

Page 44

86-86000-00 B02 - Page 473. OperationTable 3-1: Local Settings.Display Factory setting OptionsLanguage English French, Spanish, German, ItalianDate/t

Page 45 - AC INPUT

86-86000-00 B02 - Page 3ContentsImportant Safety Instructions ...

Page 46 - 86-86000-00 B02 - Page 44

86-86000-00 B02 - Page 483. OperationTable 3-3: ON/OFF Features.Display Factory setting Options CommentsCold start Disabled Enabled Start on battery.

Page 47 - 3. Operation

86-86000-00 B02 - Page 493. Operation3.3 Information Technology IT Network and Industrial Operating ModesTable 3-5: System Operation in IT Netowrk a

Page 48

86-86000-00 B02 - Page 503. Operation3.3.1 UPS personalization through external softwareInsert the Solution-Pac 2 CD ROM in your CD drive.At the firs

Page 49 - 86-86000-00 B02 - Page 47

86-86000-00 B02 - Page 513. Operation3.4 Operating Modes3.4.1 Normal (Double Conversion) ModeFigure 3-4: Normal (Double Conversion) Mode.OFFONOFFON

Page 50

86-86000-00 B02 - Page 523. Operation3.4.2 ECO ModeFigure 3-5: ECO Mode Display. OFF ON15 17OFF ON15 16OFF ON15The main advantage of the ECO mode is

Page 51

86-86000-00 B02 - Page 533. Operation3.5 Operation on Battery PowerFigure 3-6: Transfer, Threshold and End of back-up time.OFF ONOFF ON 15 16REMAINI

Page 52

86-86000-00 B02 - Page 543. Operation3.6 Return of Normal AC sourceAfter an outage, the UPS restarts automatically when AC power is restored (unless

Page 53

86-86000-00 B02 - Page 554. Maintenance4.0 ScopeMaintenance includes a troubleshooting guide of symptoms and possible solutions, hot swapping the Pow

Page 54

86-86000-00 B02 - Page 564. MaintenanceTable 4-2: Troubleshooting Requiring EATON After-Sales Support.Symptoms Indication CorrectionLED 17 and 18 are

Page 55

86-86000-00 B02 - Page 574. Maintenance4.2 Hot Swapping the Power ModuleThis operation can be performed without interrupting the load.Figure 4-1: Di

Page 56

86-86000-00 B02 - Page 43. Operation 3.0 .. Scope ...

Page 57 - 4. Maintenance

86-86000-00 B02 - Page 584. Maintenance4.3 Re-Connecting the Power ModuleThis operation can be performed without interrupting the load.Figure 4-2: R

Page 58

86-86000-00 B02 - Page 594. Maintenance4.4 Hot Swapping the Battery ModuleDuring the replacement of the Battery Module, it is imperative to use the s

Page 59

86-86000-00 B02 - Page 60(This page left blank intentionally)

Page 60

86-86000-00 B02 - Page 615. Appendix5.0 Electrical SpecificationsElectrical and Mechanical specifications for the EX RT 5/7/11.5.1 System Input/Outp

Page 61 - Battery ModulePower Module

86-86000-00 B02 - Page 625. Appendix5.3 System Back-Up CharacteristicsTable 5-2: Back-Up Time (In Minutes).11 kVA With 9 Ah Battery Modules: 10% 20%

Page 62 - 86-86000-00 B02 - Page 60

86-86000-00 B02 - Page 635. AppendixTable 5-3: Battery Recharge Time to Recover 90% of the Rated Back-Up Time After Discharge at Full Load. Configura

Page 63 - 5. Appendix

86-86000-00 B02 - Page 645. AppendixTable 5-7: Efficiency on ECO Mode (All Kinds of Load) and Batteries Fully Charged. kVA / kW 25% 50% 75% 100% Out

Page 64

86-86000-00 B02 - Page 65EATON Customer Care Center Technical Support and Product Services?Technical questions? If you encounter a problem while foll

Page 65

86-86000-00 B02 - Page 66

Page 66

86-86000-00 B02 - Page 675. Appendix5.8 GlossaryTerm used Definition/Meaning@At./And/or.+/-Plus or Minus.≤Equal to or less than.#Number.°CDegree Cels

Page 67 - 86-86000-00 B02 - Page 65

86-86000-00 B02 - Page 5FiguresFigure Description ...

Page 68 - 86-86000-00 B02 - Page 66

86-86000-00 B02 - Page 685. AppendixdBrnCDecibel above reference noise.DC or dcDirect current, or voltage.Earth groundA ground circuit that has contac

Page 69

86-86000-00 B02 - Page 695. AppendixOSHAOccupational Safety and Health Agency.PCAPrinted circuit assembly.PCBPrinted circuit board.PNPart number.PWMPu

Page 70

86-86000-00 B02 - Page 70(This page left blank intentionally)

Page 71

Recorder FormEaton Corporation8609 Six Forks Road Raleigh, North Carolina 27615 USAUse this form to report any errors, omissions, or other probl

Page 74

www.eaton.com86-86000-00 B02

Page 75

86-86000-00 B02 - Page 64-1: Disconnecting the Power Module ...... 574-2: R

Page 76 - 86-86000-00 B02

86-86000-00 B02 - Page 7(This page right blank intentionally)